WSCC EDDY Co. - History Log
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. The WSCC Eddy Co. Tie will be limited to 130 in both directions as a result of planned maintenance from 1/16/2023 1100 (CD) until 12/31/2023 0100 am (CD) |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. The WSCC Eddy Co. Tie will be limited to 130 in both directions as a result of planned maintenance from 1/16/2023 1100 (CD) until 12/31/2023 0100 am (CD) |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. The WSCC Eddy Co. Tie will be limited to 130 in both directions as a result of planned maintenance from 1/16/2023 1100 (CD) until 12/31/2023 0100 am (CD) |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. The WSCC Eddy Co. Tie will be limited to 130 in both directions as a result of planned maintenance from 1/16/2023 1100 (CD) until 12/31/2023 0100 am (CD) |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. The WSCC Eddy Co. Tie will be limited to 130 in both directions as a result of planned maintenance from 1/16/2023 1100 (CD) until 12/31/2023 0100 am (CD) |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. The WSCC Eddy Co. Tie will be limited to 130 in both directions as a result of planned maintenance from 1/16/2023 1100 (CD) until 12/31/2023 0100 am (CD) |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. The WSCC Eddy Co. Tie will be limited to 130 in both directions as a result of planned maintenance from 1/16/2023 1100 (CD) until 12/31/2023 0100 am (CD) |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. The WSCC Eddy Co. Tie will be limited to 130 in both directions as a result of planned maintenance from 1/16/2023 1100 (CD) until 12/31/2023 0100 am (CD) |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. The WSCC Eddy Co. Tie will be limited to 130 in both directions as a result of planned maintenance from 1/16/2023 1100 (CD) until 12/31/2023 0100 am (CD) |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. The WSCC Eddy Co. Tie will be limited to 130 in both directions as a result of planned maintenance from 1/16/2023 1100 (CD) until 12/31/2023 0100 am (CD) |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. The WSCC Eddy Co. Tie will be limited to 130 in both directions as a result of planned maintenance from 1/16/2023 1100 (CD) until 12/31/2023 0100 am (CD) |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. The WSCC Eddy Co. Tie will be limited to 130 in both directions as a result of planned maintenance from 1/16/2023 1100 (CD) until 12/31/2023 0100 am (CD) |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. The WSCC EDDY Co. DC Tie in both directions will be limited to 0 as a result of unplanned maintenance from 8/28/2023 0400 AM (CD) to 8/30/2023 0100 (CD). The WSCC Eddy Co. Tie will be limited to 130 in both directions as a result of planned maintenance from 1/16/2023 1100 (CD) until 12/31/2023 0100 am (CD) |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. The WSCC EDDY Co. DC Tie in both directions will be limited to 0 as a result of unplanned maintenance from 8/28/2023 0400 AM (CD) to 8/30/2023 0100 (CD). The WSCC Eddy Co. Tie will be limited to 130 in both directions as a result of planned maintenance from 1/16/2023 1100 (CD) until 12/31/2023 0100 am (CD) |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. The WSCC EDDY Co. DC Tie in both directions will be limited to 0 as a result of unplanned maintenance from 8/28/2023 0400 AM (CD) to 8/29/2023 0100 (CD). The WSCC Eddy Co. Tie will be limited to 130 in both directions as a result of planned maintenance from 1/16/2023 1100 (CD) until 12/31/2023 0100 am (CD) |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. The WSCC EDDY Co. DC Tie in both directions will be limited to 0 as a result of unplanned maintenance from 8/28/2023 0400 AM (CD) to 8/28/2023 1700 (CD). The WSCC Eddy Co. Tie will be limited to 130 in both directions as a result of planned maintenance from 1/16/2023 1100 (CD) until 12/31/2023 0100 am (CD) |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. The WSCC EDDY Co. DC Tie in both directions will be limited to 0 as a result of unplanned maintenance from 8/28/2023 0400 AM (CD) to 8/28/2023 1700 (CD). |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. The Eddy Tie will be conducting test between 10:00 to 12:00 on 3/18/2016 |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. 4/13/2015 16:00 Eddy DC Tie will be available for testing purposes only from 4/14/2015 09:00(CDT) - 4/16/2015 00:00(CDT) |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. 4/13/2015 16:00 Eddy DC Tie will be available for testing purposes only from 4/14/2015 09:00(CDT) - 4/16/2015 00:00(CDT) |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. 4/13/2015 16:00 Eddy DC Tie will be available for testing purposes only from 4/14/2015 09:00(CDT) - 4/16/2015 00:00(CDT) |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. 4/13/2015 16:00 Eddy DC Tie will be available for testing purposes only from 4/14/2015 09:00(CDT) - 4/16/2015 00:00(CDT) |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. 4/13/2015 16:00 Eddy DC Tie will be available for testing purposes only from 4/14/2015 09:00(CDT) - 4/16/2015 00:00(CDT) |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff. |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff |
| El Paso Electric has posted a Business Practice on the EPE OASIS regarding operation of the Eddy County HVDC tie. Customers requesting transmission service under the SPP OATT for service up to or out of the Eddy HVDC tie are responsible for reading and understanding this EPE Business Practice. The customer should also understand that any transmission service charges for reservations under the SPP OATT up to or out of the EDDY HVDC tie will not be forgiven when the Eddy HVDC tie becomes inoperable due to this EPE Business Practice. Questions related to the EPE Business Practices or status of the Eddy HVDC Tie due to this Business Practice should be directed to the EPE OASIS or EPE Staff |
| EPE states that the minimum flow for the EDDY tie is 35MW 0612 hours on 10/25/2011 The Eddy Co DC tie is available for full capability subject to El Paso Business Practices. |
| EPE states that the minimum flow for the EDDY tie is 35MW 0612 hours on 10/25/2011 The Eddy Co DC tie is available for full capability subject to El Paso Business Practices. |
| EPE states that the minimum flow for the EDDY tie is 35MW 0717 hours on 10/24/2011 The Eddy Co DC tie is available for full capability subject to El Paso Business Practices. |
| EPE states that the minimum flow for the EDDY tie is 35MW 0717 hours on 10/24/2011 The Eddy Co DC tie is out of service for maintenance. ETR is 13:00 on 10/24/2011. |
| EPE states that the minimum flow for the EDDY tie is 35MW 8/2/2011 The Eddy Co DC tie is available for full capability. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy Co DC tie has tripped offline at 2132 on 7/30/11 CDT. The return to service time is @ 1200 on 8/2/11. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy Co DC tie has tripped offline at 2132 on 7/30/11 CDT. The return to service time is unknown. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy Co DC tie has tripped offline at 1449 on 7/30/11 CDT. The return to service time is 1855 on 7/30/11. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy Co DC tie has tripped offline at 1449 on 7/30/11 CDT. The return time is expected to be 1900 on 7/30/11. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy Co DC tie has tripped offline at 1449 on 7/30/11 CDT. The cause is unknown at this time and there is no estimate of what time it will be restored. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy Co DC tie return to service at 1700 on 7/27/11 CDT. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy Co DC tie tripped at 1230 CDT on 7/25/2011.Return time is 1700 on 7/27/11 CDT. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy Co DC tie tripped at 1230 CDT on 7/25/2011.Return time unknown. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy Co DC tie is returned to service as of 1800 7/23/2011. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy Co DC tie is out of service as of 23:45 7/22/2011.The estimated time of return is 7/23/2011 at 2300. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy Co DC tie is back in service as of 15:49 7/09/2011. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy Co tie is back in service as of 15:49 7/09/2011. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy Co tie tripped at 08:11 on 7-3-11. ETR is 1700 7/11/2011. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy Co tie triped at 08:11 on 7-3-11. As of 17:15CDT on 07/06/2011, the DC Tie has not been restored to service. No ETR. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy Co tie triped at 08:11 on 7-3-11. As of 16:15CDT on 07/06/2011, the expected return time is 17:00 on 07-06-11 |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy Co tie triped at 08:11 on 7-3-11. As of 15:42 on 07/06/2011, the projected return time is 17:00 on 07-06-11 |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy Co tie triped at 08:11 on 7-3-11. As of 15:4207/06/2011, the projected return time is 17:00 on 07-06-11 |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy Co tie triped at 08:11 on 7-3-11.As of 15:4207/06/2011, the estimated return time is 17:00 on 07-06-11 |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy Co tie triped at 08:11 on 7-3-11.As of 15:4207/06/2011, the estimated return time is 17:00 on 07-06-11 |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy Co tie triped at 08:11 on 7-3-11 return time 17:00 on 07-06-11 |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy Co tie triped at 08:11 on 7-3-11 return time 17:00 on 07-05-11 |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy Co tie triped at 08:11 return time unknown 07/03/11 |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy Co tie is available for full service at 1607 6/24/2011. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy Co tie will be unavailable starting at noon 6/23/2011 until noon 6/24/2011 due to a cooling problem. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy Co tie is available on 02/11/2011 at 15:00. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy Co tie is unavailable to investigate problem with HVDC at 18:00CST on 02/09/2011. ETR 15:00CST on 2/11/11. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy Co tie is available for service at 00:00 on 02/03/2011. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy Co tie has tripped and is unavailable for service at 00:00 on 02/03/2011. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy Co tie has tripped and is unavailable for service at 19:30 on 02/02/2011. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy Co tie is available for service at 0600 on 12/9/2010. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy Co. DC tie tripped off line at 0202 on 12-8-10. The estimated time of return to service is unknown at this time. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy Co. DC tie was returned to service at 1730 on 10-11-10. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy Co. DC tie was returned to service at 1730 on October 11th. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy Co. DC tie was taken out of service at 1600 on October 10th and will be returned to service at 1730 on October 11th. |
| EPE states that the minimum flow for the EDDY tie is 35MW No outage scheduled for this time. |
| EPE states that the minimum flow for the EDDY tie is 35MW No outage scheduled for this time. |
| EPE states that the minimum flow for the EDDY tie is 35MW No outage scheduled for this time. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy DC Tie is available, but a two (2) hour notice is required to schedule on this tie. |
| EPE states that the minimum flow for the EDDY tie is 35MW Two hour notice is required to schedule on this tie. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy Co. DC Tie is back in service as of 1700 CST on 12-29-09. Two hour notice is required to schedule on this tie. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy Co. DC Tie is back in service as of 1700 CST on 12-29-09. Two hour notice is required to schedule on this tie. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy Co. DC Tie is back in service as of 1700 CST on 12-29-09. Two hour notice is required to schedule on this tie. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy Co. Tie is back in service as of 1700 CST on 12-29-09. Two hour notice is required to schedule on this tie. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy Co. Tie is back in service as of 1700 CST on 12-29-09. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy Co. Tie is back in service as of 1700 CST on 12-29-09, but SPS requires a 2 hour notice to schedule across the tie due to having to start oil pumps. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy Co. Tie is out of service as of 1700 CST on 12-22-09. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy Co. Tie is available for full capability as of 0613 CST on 12-07-09. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy Co. Tie is available as |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy DC Tie will be out of service from Oct 26th at 0900 until Dec 1st at 1700. The Eddy DC Tie is still out of service at this time 1500 12-2-09.Estimated time to return is unknown at this time |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy DC Tie will be out of service from Oct 26th at 0900 until Dec 1st at 1700. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy DC Tie will be out of service from Oct 26th at 0900 thru Nov 18th at 1700. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy DC Tie will be out of service from Oct 26th at 0900 thru Nov 13th at 1730. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy DC Tie will be out of service from Oct 26th at 0900 thru Nov 6th at 1700. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy DC Tie returned to full service at 1200 CDT on 6/24/09. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy DC Tie will be out of service from 6/19/09 at 1600 CDT thru 6/24/09 at 1200 CDT. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy DC Tie will be out of service from 6/19/09 at 1600 CDT thru 6/23/09 at 1800 CDT. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy DC Tie returned to full service on 5/18/2009 at 1700CDT |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy DC Tie is out of service for repairs. It is scheduled to return to service on 5/18/2009 at 1700CDT |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy DC Tie is out of service for repairs. It is scheduled to return to service on 5/14/2009 at 1200CDT |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy DC Tie is out of service for repairs. It is scheduled to return to service on 5/13/2009 at 2200CDT |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy DC Tie is out of service for repairs. It is scheduled to return to service on 5/11/2009 at 1300CDT |
| EPE states that the minimum flow for the EDDY tie is 35MW Normal operations |
| EPE states that the minimum flow for the EDDY tie is 35MW Eddy tie has been returned to normal service as of 1800 CDT 3/26/09. |
| EPE states that the minimum flow for the EDDY tie is 35MW Eddy tie is limited to 100 mw from 3/20/09 at 1700 CDT thru 3/27/09 at 1700 CDT. |
| EPE states that the minimum flow for the EDDY tie is 35MW Eddy tie is limited to 100 mw from 3/20/09 at 1700 CDT thru 3/27/09 at 1700. |
| EPE states that the minimum flow for the EDDY tie is 35MW Eddy tie is out of service as of 00:00 on 01-26-2009 ETR: 14:00 (CDT) on 03-09-2009. |
| EPE states that the minimum flow for the EDDY tie is 35MW Eddy tie is out of service as of 00:00 on 01-26-2009 ETR: 18:00 (CDT) on 03-09-2009. |
| EPE states that the minimum flow for the EDDY tie is 35MW Eddy tie is out of service as of 00:00 on 01-26-2009 ETR: 18:00 (CDT) on 04-27-2009. |
| EPE states that the minimum flow for the EDDY tie is 35MW Eddy tie is out of service as of 00:00 on 01-26-2009 ETR: 17:00 on 04-10-2009. |
| EPE states that the minimum flow for the EDDY tie is 35MW Eddy tie is out of service as of 00:00 on 01-26-2009 ETR: 17:00 on 02-06-2009. |
| EPE states that the minimum flow for the EDDY tie is 35MW Eddy tie is out of service from 00:00 on 01-26-2009 ETR: 00:00 on 01-31-2009. |
| EPE states that the minimum flow for the EDDY tie is 35MW No scheduled outages |
| EPE states that the minimum flow for the EDDY tie is 35MW No scheduled outages |
| EPE states that the minimum flow for the EDDY tie is 35MW Eddy Tie will be out of service from 1/9/09 11:30 to 1/9/09 15:00 |
| EPE states that the minimum flow for the EDDY tie is 35MW The EDDY DC Tie is back in service as of 1800 12/20/08 |
| EPE states that the minimum flow for the EDDY tie is 35MW |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy Co DC tie is currently out of service as of 1025 on 12/20/08 due to a needed repair. It is estimated to return to service at 1500 on 12/20/08 |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy Co DC tie restored at 1630 CST on 12/4/08.br> |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy Co DC tie will be unavailable from 12-01-2008 @16:06 (CST) to 12-05-2008 @ 18:00 (CST) due to a forced outage. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy DC tie has returned to service at 1500 CST on 11/03/08. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy dc tie is out of service at 0800 CDT on 10/24/08. Estimated return to service is 11/03/08 @ 1700 hrs. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy dc tie is out of service at 0800 CDT on 10/24/08. Estimated return to service 11/03/08 @ 1700 hrs. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy dc tie is out of service at 0800 CDT on 10/24/08. Estimated return to service 10/31/08 @ 1700 hrs. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy dc tie is out of service at 0800 CDT on 10/24/08. Estimated return to service 10/28/08 @ 1700 hrs. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy dc tie is out of service at 0800 CDT on 10/24/08. Estimated return to service 10/27/08 @ 1700 hrs. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy dc tie is out of service at 1400 CDT on 10/16/08. Estimated return to service 10/22/08 @ 1700 hrs. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy dc tie is out of service at 1400 CDT on 10/16/08. Estimated return to service 10/17/08 1700 hrs. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy dc tie is out of service at 1400 CDT on 10/16/08. Estimated return to service To Be Determined. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy dc tie is out of service at 1400 CDT on 10/16/08 Estimated return to service To Be Determined. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy dc tie back in service at 1511 CDT on 14 Oct. 08. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy dc tie tripped at 1022 on 10-2-2008 and will not return to service until 1511 CDT on 14 Oct. 08. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy dc tie tripped at 1022 on 10-2-2008 and will not return to service until 0800 CDT on 15 Oct. 08. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy dc tie tripped at 1022 on 10-2-2008 and will not return to service until 1800 CDT on 15 Oct. 08. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy dc tie tripped at 1022 on 10-2-2008 and will not return to service until 1800 CDT on 10 Oct. 08. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy dc tie tripped at 1022 on 10-2-2008 and will not return to service until 2300 CDT on 2 Oct. 08. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy dc tie tripped at 1527 on 9-28-2008 and will not return to service until 1600 on 1 Oct. 08. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy dc tie tripped at 1527 on 9-28-2008. The EDDY CO. tie is scheduled out of service at 0400 9/23/08 for 2 hours. |
| EPE states that the minimum flow for the EDDY tie is 35MW The EDDY CO. tie is scheduled out of service at 0400 9/23/08 for 2 hours. |
| EPE states that the minimum flow for the EDDY tie is 35MW The EDDY CO. is back to normal at 1536. |
| EPE states that the minimum flow for the EDDY tie is 35MW The EDDY CO. dc tie tripped at 1600 on 9/13/08. Return time is 9/17/08 at 0000 . |
| EPE states that the minimum flow for the EDDY tie is 35MW The EDDY CO. dc tie tripped at 1600 on 9/13/08. Return time is 9/16/08 at 0000 . |
| EPE states that the minimum flow for the EDDY tie is 35MW No scheduled outages at this time. . |
| EPE states that the minimum flow for the EDDY tie is 35MW Eddy Tie tripped at 1515 27 July 08. Return time is scheduled for August 8th at 1800 . No scheduled outages at this time. |
| EPE states that the minimum flow for the EDDY tie is 35MW Eddy Tie tripped at 1515 27 July 08. Return time is scheduled for August 4th at 1800 . No scheduled outages at this time. |
| EPE states that the minimum flow for the EDDY tie is 35MW Eddy Tie tripped at 1515 27 July 08. Return time is scheduled for August 4th . No scheduled outages at this time. |
| EPE states that the minimum flow for the EDDY tie is 35MW Eddy Tie tripped at 1515 27 July 08. Return time is scheduled for 31st July 08 at 1900 cdt. No scheduled outages at this time. |
| EPE states that the minimum flow for the EDDY tie is 35MW Eddy Tie tripped at 1515 27 July 08. Return time is scheduled for 29th July 08 at 1900 cdt. No scheduled outages at this time. |
| EPE states that the minimum flow for the EDDY tie is 35MW Eddy Tie tripped at 1515 27 July 08. Return time is scheduled for 30th July 08 at 1900 cdt. No scheduled outages at this time. |
| EPE states that the minimum flow for the EDDY tie is 35MW Eddy Tie tripped at 1515 27 July 08. Return time is scheduled for 29th July 08 at 1900 cdt. No scheduled outages at this time. |
| EPE states that the minimum flow for the EDDY tie is 35MW Eddy Tie tripped at 1515 27 July 08. Return time is scheduled for 28th July 08 at 1700 cdt. No scheduled outages at this time. |
| EPE states that the minimum flow for the EDDY tie is 35MW Eddy Tie tripped at 1515 27 July 08. Return time unknown. No scheduled outages at this time. |
| EPE states that the minimum flow for the EDDY tie is 35MW Eddy Tie is back in service at 1200 on 7/22/08 No scheduled outages at this time. |
| EPE states that the minimum flow for the EDDY tie is 35MW Eddy Tie tripped out of service on 7/18/08 1113 hours. Return to service scheduled for 7/22/08 1700 hour. |
| EPE states that the minimum flow for the EDDY tie is 35MW No outages scheduled at this time. |
| EPE states that the minimum flow for the EDDY tie is 35MW The EDDY Co. DC tie returned to service at 1735 hours on 7.11.08. |
| EPE states that the minimum flow for the EDDY tie is 35MW The EDDY Co. DC tie tripped at 1443 hours on 7.11.08. ETR is 1800 hours on 7.11.08. |
| EPE states that the minimum flow for the EDDY tie is 35MW The EDDY Co. DC tie returned to service at 1700 on 7/3/08. |
| EPE states that the minimum flow for the EDDY tie is 35MW The EDDY Co. DC tie has tripped out of servie as of 2300 on 7/2/08. Return time TBD. |
| EPE states that the minimum flow for the EDDY tie is 35MW The EDDY Co. DC tie has tripped out of servie. Return time TBD. |
| EPE states that the minimum flow for the EDDY tie is 35MW The EDDY Co. DC tie is available and there are no outages scheduled at this time |
| EPE states that the minimum flow for the EDDY tie is 35MW The EDDY Co. DC tie is out of service as of 1258CDT 6/2/08. Return expected at 2300CDT 6/3/08. Vale hall problems. |
| EPE states that the minimum flow for the EDDY tie is 35MW The EDDY Co. DC tie is out of service as of 1258CDT 6/2/08. Return expected at 1700CDT 6/2/08. Vale hall problems. |
| EPE states that the minimum flow for the EDDY tie is 35MW The EDDY Co. DC tie is back in service as of 6/1/08 @ 2130 hour. |
| EPE states that the minimum flow for the EDDY tie is 35MW The EDDY Co. DC tie will be unavailable from 6/1/08 at 0145 cdt thru 6/2/08 at 1700 cdt. The cause of the outage is unknown. |
| EPE states that the minimum flow for the EDDY tie is 35MW The EDDY Co. DC tie will be unavailable from 5/30/08 at 0100 cdt thru 0900 cdt. |
| EPE states that the minimum flow for the EDDY tie is 35MW The EDDY Co. DC tie will be unavailable from 4/12/08 at 0200 CDT thru 1800 CDT on 4/20/08. |
| EPE states that the minimum flow for the EDDY tie is 35MW No scheduled outages at this time. |
| EPE states that the minimum flow for the EDDY tie is 35MW Eddy HVDC won't start. Unknown reason. Tie is unavailable at this time. Waiting on "SCR" parts. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy Co tie was placed back in service at 0100 on 2/5/08. The EDDY CO tie is back in service . |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy Co tie was placed back in service at 0100 on 2/5/08. The EDDY CO tie tripped @ 01:52 on Feb 13, 2008 and will be out of service for a few hours. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy Co tie was placed back in service at 0100 on 2/5/08. The EDDY CO tie will be derated to 133 mw East to West direction starting at 0700 on 1/21/08 thru 1800 on 2/08/08 due to line outage. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy Co tie was placed back in service at 0100 on 2/5/08. The Eddy Co. tie tripped at approximately 1240 on 2/4/08. Return time unkown at this time. The EDDY CO tie will be derated to 133 mw East to West direction starting at 0700 on 1/21/08 thru 1800 on 2/08/08 due to line outage. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy Co. tie tripped at approximately 1240 on 2/4/08. Return time unkown at this time. The EDDY CO tie will be derated to 133 mw East to West direction starting at 0700 on 1/21/08 thru 1800 on 2/08/08 due to line outage. |
| EPE states that the minimum flow for the EDDY tie is 35MW The EDDY CO tie will be derated to 133 mw East to West direction starting at 0700 on 1/21/08 thru 1800 on 2/08/08 due to line outage. |
| EPE states that the minimum flow for the EDDY tie is 35MW EDDY CO Tie is back in service at 1735 on 1/24/08. The EDDY CO tie will be derated to 133 mw East to West direction starting at 0700 on 1/21/08 thru 1800 on 2/08/08 due to line outage. |
| EPE states that the minimum flow for the EDDY tie is 35MW EDDY CO Tie is back in service at 1735 on 1/24/08. The EDDY CO tie will be derated to 133 mw East to West direction starting at 0700 on 1/21/08 thru 1800 on 2/08/08 due to line outage.br> |
| EPE states that the minimum flow for the EDDY tie is 35MW EDDY CO Tie is relased to service at 1735 on 1/24/08. The EDDY CO tie will be derated to 133 mw East to West direction starting at 0700 on 1/21/08 thru 1800 on 2/08/08 due to line outage.br> |
| EPE states that the minimum flow for the EDDY tie is 35MW Tie is out of service as of 0100 hours on 01/16/08 until 1/26/08 at 2300 cst.. The EDDY CO tie will be derated to 133 mw East to West direction starting at 0700 on 1/21/08 thru 1800 on 2/08/08 due to line outage.br> |
| EPE states that the minimum flow for the EDDY tie is 35MW Tie is out of service as of 0100 hours on 01/16/08 until further notice. The EDDY CO tie will be derated to 133 mw East to West direction starting at 0700 on 1/21/08 thru 1800 on 2/08/08 due to line outage.br> |
| EPE states that the minimum flow for the EDDY tie is 35MW Tie is back in service as of 1854 hours on 01/15/08. The EDDY CO tie will be derated to 133 mw East to West direction starting at 0700 on 1/21/08 thru 1800 on 2/08/08 due to line outage.br> |
| EPE states that the minimum flow for the EDDY tie is 35MW Tie Tripped @ 13:17. ETA Unknown. The EDDY CO tie will be derated to 133 mw East to West direction starting at 0700 on 1/21/08 thru 1800 on 2/08/08 due to line outage.br> |
| EPE states that the minimum flow for the EDDY tie is 35MW tie tripped 13:17. ETA Ubknown. The EDDY CO tie will be derated to 133 mw East to West direction starting at 0700 on 1/21/08 thru 1800 on 2/08/08 due to line outage.br> |
| EPE states that the minimum flow for the EDDY tie is 35MW The EDDY CO tie will be derated to 133 mw East to West direction starting at 0700 on 1/21/08 thru 1800 on 2/08/08 due to line outage.br> |
| EPE states that the minimum flow for the EDDY tie is 35MW There are no scheduled outages on the Eddy Co. Tie at this time. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Tolk – Eddy Co 345kV circuit will be out of service 12/10/2007 – 12/21/2007 daily from 07:00 – 18:00 and returning to service at night. SPS has requested that the Eddy Co DC Tie be limited to 40MW East to West while the Tolk – Eddy Co is out of service. |
| EPE states that the minimum flow for the EDDY tie is 35MW There are no scheduled outages on the EDDY CO. tie at this time.. |
| EPE states that the minimum flow for the EDDY tie is 35MW The EDDY CO. tie is back to normal. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Annual Maintenance for the EDDY CO. tie is scheduled for 12/01/07 at 0200 CST thru 12/07/07 at 1800CST. |
| EPE states that the minimum flow for the EDDY tie is 35MW Eddy Co. tie tripped @ 2314 24 Nov 07, return time 2358 24 Nov 07. The Annual Maintenance for the EDDY CO. tie is scheduled for 12/01/07 at 0200 CST thru 12/07/07 at 1800CST. |
| EPE states that the minimum flow for the EDDY tie is 35MW Eddy Co. tie tripped @ 2314 24 Nov 07, return time unknown. The Annual Maintenance for the EDDY CO. tie is scheduled for 12/01/07 at 0200 CST thru 12/07/07 at 1800CST. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Annual Maintenance for the EDDY CO. tie is scheduled for 12/01/07 at 0200 CST thru 12/07/07 at 1800CST. |
| EPE states that the minimum flow for the EDDY tie is 35MW There are no scheduled outages on the Eddy Tie at this time. |
| EPE states that the minimum flow for the EDDY tie is 35MW The EddY Co tie was restored at 1700 on 8/30/07 There are no scheduled outages on the Eddy Tie at this time. |
| EPE states that the minimum flow for the EDDY tie is 35MW The EddY Co tie was restored at 1700 on 8/30/07br> There are no scheduled outages on the Eddy Tie at this time. |
| EPE states that the minimum flow for the EDDY tie is 35MW The EddY Co tie will be derated to 60mw East to West direction from 8/27/07 at 1200 thru 8/30/07 at 1700. There are no scheduled outages on the Eddy Tie at this time. |
| EPE states that the minimum flow for the EDDY tie is 35MW There are no scheduled outages on the Eddy Tie at this time. |
| EPE states that the minimum flow for the EDDY tie is 35MW EDDY CO. DC tie back in service @ 1830 on 4/11/07 |
| EPE states that the minimum flow for the EDDY tie is 35MW EDDY CO. DC tie out of service from 4/1/07 @ 1700 thru 4/30/07 @ 1700 |
| EPE states that the minimum flow for the EDDY tie is 35MW EDDY CO. DC tie out of service from 4/1/07 @ 1700 thru 4/5/07 @ 1700 br> |
| EPE states that the minimum flow for the EDDY tie is 35MW March 24th @16:00 CST. Released to full load, East to West flow only, West to East at "0" mws for control problems |
| EPE states that the minimum flow for the EDDY tie is 35MW March 23th @13:00 CST. Released to full load East to West flow only, West to East at "0" mws for control problems |
| EPE states that the minimum flow for the EDDY tie is 35MW March 23th @13:00 CST. Released to full load East or West. |
| EPE states that the minimum flow for the EDDY tie is 35MW March 18th @18:00 CST. Released to full load East to West only. |
| EPE states that the minimum flow for the EDDY tie is 35MW Scheduled Outage on March 10th @09:00 CST to March 18th @18:00 CST. |
| EPE states that the minimum flow for the EDDY tie is 35MW scheduled outage on March 10th @09:00 CST to March 18th @18:00 CST. |
| EPE states that the minimum flow for the EDDY tie is 35MW No scheduled outages at this time |
| EPE states that the minimum flow for the EDDY tie is 35MW The EDDY CO tie back in service at 0745 12/13/06. No scheduled outages at this time |
| EPE states that the minimum flow for the EDDY tie is 35MW The EDDY Co would not start at 0700 CST on 12/13/06. Cause unknown at this time. No scheduled outages at this time |
| EPE states that the minimum flow for the EDDY tie is 35MW No scheduled outages at this time |
| EPE states that the minimum flow for the EDDY tie is 35MW No scheduled outages at this time |
| EPE states that the minimum flow for the EDDY tie is 35MW No scheduled outages at this time |
| EPE states that the minimum flow for the EDDY tie is 35MW EDDY CO tie back in service at 0600 on 11/29/06 No scheduled outages at this time |
| EPE states that the minimum flow for the EDDY tie is 35MW EDDY Tie has tripped out of service. EDDY Tie will be out until further notice |
| EPE states that the minimum flow for the EDDY tie is 35MW There are no outages scheduled at this time |
| EPE states that the minimum flow for the EDDY tie is 35MW EDDY DC tie is scheduled to be out of service from 11/12/06 @ 1200 CS thru 11/19/06 @ 1800 cs. |
| EPE states that the minimum flow for the EDDY tie is 35MW EDDY DC tie is scheduled to be out of service from 11/12/06 @ 1100 CS thru 11/19/06 @ 1700 cs. |
| EPE states that the minimum flow for the EDDY tie is 35MW EDDY DC tie is scheduled to be out of service from 11/13/06 @ 0700 CS thru 11/19/06 @ 1730 cs. |
| EPE states that the minimum flow for the EDDY tie is 35MW EDDY DC tie back in service as of 2055CST 4 Nov 06. |
| EPE states that the minimum flow for the EDDY tie is 35MW Eddy DC tie tripped 10/14/06 1400CDT. EDDY DC tie back in service as of 2055CST 4 Nov 06. |
| EPE states that the minimum flow for the EDDY tie is 35MW Eddy DC tie tripped 10/14/06 1400CDT. EDDY DC tie back in service as of 2055CST 4 Nov 06. |
| EPE states that the minimum flow for the EDDY tie is 35MW Eddy DC tie tripped 10/14/06 1400CDT. Due to continuing problems tie is unavailable until further notice. |
| Eddy DC tie tripped 10/14/06 1400CDT. Due to continuing problems tie is unavailable until further notice. EPE states that the minimum flow for the EDDY tie is 35MW |
| Eddy DC tie tripped 10/14/06 1400CDT. Due to continuing problems tie is unavailable until further notice. EPE states that the minimum flow for the EDDY tie is 35MW |
| Eddy DC tie tripped 10/14/06 1400CDT. Due to continuing problems tie is unavailable until further notice. EPE states that the minimum flow for the EDDY tie is 35MW |
| EPE states that the minimum flow for the EDDY tie is 35MW Eddy DC tie tripped 10/14/06 1400CDT. Due to continuing problems tie is unavailable until further notice. |
| EPE states that the minimum flow for the EDDY tie is 35MW Eddy DC tie tripped 10/14/06 1400CDT. Due to continuing problems tie is unavailable until possibily 10/20/06 1800CDT. |
| EPE states that the minimum flow for the EDDY tie is 35MW Eddy DC tie tripped 10/14/06 1400CDT. Due to continuing problems tie is unavailable until possibily 10/19/06 0200CDT. |
| EPE states that the minimum flow for the EDDY tie is 35MW Eddy DC tie tripped 10/14/06. Due to continuing problems tie is unavailable until possibily 10/19/06. |
| EPE states that the minimum flow for the EDDY tie is 35MW |
| EPE states that the minimum flow for the EDDY tie is 35MW The EDDY Co HVDC tie will be off line from 0600 MDT until 1200 MDT on 8/31/06 for replacement of failed equipment. |
| EPE states that the minimum flow for the EDDY tie is 35MW There are no outages scheduled at this time. |
| EPE states that the minimum flow for the EDDY tie is 35MW The Eddy Co tie back in service at 2018 on May 10th. There are no outages scheduled at this time. |
| EPE states that the minimum flow for the EDDY tie is 35MW At 1313 CDT the Eddy County tie tripped off line. Scheduled to be back in service at 1300 on May 10,2006. There are no outages scheduled at this time. |
| EPE states that the minimum flow for the EDDY tie is 35MW At 1313 CDT the Eddy County tie tripped off line. Scheduded to be back in service at 1300 on May 10,2006. There are no outages scheduled at this time. |
| EPE states that the minimum flow for the EDDY tie is 35MW There are no outages scheduled at this time. |
| EPE states that the minimum flow for the EDDY tie is 35MW The EDDY DC tie is available as of 0334CDT 2 Apr 06. There are no outages scheduled at this time. |
| EPE states that the minimum flow for the EDDY tie is 35MW The EDDY DC tie is available as of 0334 2 Apr 06. There are no outages scheduled at this time. |
| EPE states that the minimum flow for the EDDY tie is 35MW The EDDY DC tie is available as of 0334 2 Apr 06. There are no scheduled outages at this time. |
| EPE states that the minimum flow for the EDDY tie is 35MW The EDDY DC tie is available as of 0334 2 Apr 06. There are no scheduled outages at this time. |
| EPE states that the minimum flow for the EDDY tie is 35MW There is a problem on the EDDY DC Tie and the tie will be shut down at 2000 1 Apr 06. The tie will be out of service until possibly Monday 3 Apr 06. |
| EPE states that the minimum flow for the EDDY tie is 35MW There are no outages scheduled at this time. |
| EPE states that the minimum flow for the EDDY tie is 35MW The following are dates the Eddy Tie will be out of service: 3/18/06 @ 0800 - 4/2/06 @ 2000 (scheduled maintenance) |
| EPE states that the minimum flow for the EDDY tie is 35MW The following are dates the Eddy Tie will be out of service: 3/18/06 @ 0800 - 4/2/06 @ 2000 (scheduled maintenance) Eddy Co. DC tie out of service for several hours due to smoothing reactor problems starting at 1800 3/5/06 |
| EPE states that the minimum flow for the EDDY tie is 35MW The following are dates the Eddy Tie will be out of service: 3/18/06 @ 0800 - 4/2/06 @ 2000 (scheduled maintenance) Eddy Co. DC tie out of service for several hours due to smoothing reactor problems |
| EPE states that the minimum flow for the EDDY tie is 35MW The following are dates the Eddy Tie will be out of service: 3/18/06 @ 0800 - 4/2/06 @ 2000 (scheduled maintenance) |
| EPE states that the minimum flow for the EDDY tie is 35MW The following are dates the Eddy Tie will be out of service: 2/17/06 @ 0200 THRU 0600 -EDDY TIE for maintenance. 3/18/06 @ 0800 - 4/2/06 @ 2000 (scheduled maintenance) |
| EPE states that the minimum flow for the EDDY tie is 35MW The following are dates the Eddy Tie will be out of service: 3/18/06 @ 0800 - 4/2/06 @ 2000 (scheduled maintenance) |
| EPE states that the minimum flow for the EDDY tie is 35MW The following are dates the Eddy Tie will be out of service: br> 3/18/06 @ 0800 - 4/2/06 @ 2000 (scheduled maintenance) |
| EPE states that the minimum flow for the EDDY tie is 35MW The following are dates the Eddy Tie will be out of service: 2/1/06 @ 0200 - 2/1/06 @ 0700 (Wiring upgrades on the 230Kv capacitors.) 3/18/06 @ 0800 - 4/2/06 @ 2000 (scheduled maintenance) |
| EPE states that the minimum flow for the EDDY tie is 35MW The following are dates the Eddy Tie will be out of service: 2/1/06 @ 2:00 - 2/1/06 @ 7:00 (Wiring upgrades on the 230Kv capacitors.) 3/18/06 @ 08:00 - 4/2/06 @ 20:00 (scheduled maintenance) |
| EPE states that the minimum flow for the EDDY tie is 35MW The following are dates the Eddy Tie will be out of service: 2/1/06 @ 2:00 - 2/1/06 @ 7:00 (Wiring upgrades on the 230Kv capacitors.) 3/18/06 @ 08:00 - 4/2/06 @ 20:00 (scheduled maintenance) |
| EPE states that the minimum flow for the EDDY tie is 35MW The following are dates the Eddy Tie will be out of service: 2/1/06 @ 2:00 - 2/1/06 @ 7:00 (scheduled maintenance) 3/18/06 @ 08:00 - 4/2/06 @ 20:00 (scheduled maintenance) |
| EPE states that the minimum flow for the EDDY tie is 35MW The following are dates the Eddy Tie will be out of service: 3/18/06 @ 08:00 - 4/2/06 @ 20:00 (scheduled maintenance) |
| EPE states that the minimum flow for the EDDY tie is 35MW Forced Maintainance Outage on the Eddy Tie from 12/14/05 1400 hour until 12/14/05 1700 hour The following are dates the Eddy Tie will be out of service: 3/18/06 @ 08:00 - 4/2/06 @ 20:00 (scheduled maintenance) |
| EPE states that the minimum flow for the EDDY tie is 35MW The following are dates the Eddy Tie will be out of service: 3/18/06 @ 08:00 - 4/2/06 @ 20:00 (scheduled maintenance) |
| EPE states that the minimum flow for the EDDY tie is 35MW The following are dates the Eddy Tie will be out of service: 12/01/05 @ 07:00 - 12/01/05 @ 15:00 (replacing moduled in the valve hall) 3/18/06 @ 08:00 - 4/2/06 @ 20:00 (scheduled maintenance) |
| EPE states that the minimum flow for the EDDY tie is 35MW The following are dates the Eddy Tie will be out of service: 12/01 07:00 - 12/01 15:00 (replacing moduled in the valve hall) 3/18 08:00 - 4/2 20:00 (scheduled maintenance) |
| EPE states that the minimum flow for the EDDY tie is 35MW There are no outages scheduled at this time. |
| EPE states that the minimum flow for the EDDY tie is 35MW There are no outages scheduled at this time. |
| EPE states minimum flow for the EDDY tie is 35MW There are no outages scheduled at this time. |
There are no outages scheduled at this time. |
There are no outages scheduled at this time.br> |
El Paso Electric canceled the maintenance outage on the Eddy HVDC due to other outages. The outage will be re-scheduled. |
El Paso Electric canceled the maintenance outage on the Eddy HVDC due outages. The outage will be re-scheduled. |
El Paso Electric canceled the maintenance outage on the Eddy HVDC due to the forced outage of units. The outage will be re-scheduled. |
El Paso Electric canceled the maintenance outage on the Eddy HVDC due to the forced outage of all three Palo Verde nuclear units. The outage will be re-scheduled. |
The EDDY Co. tie will taken out of service on 15 OCT early AM for a 9 day maintenance outage. |
TheEDDY Co. tie will taken out of service on 15 OCT early AM for a 9 day maintenance outage. |
There are no scheduled outages at this time. |
EDDY Tie is back in service. |
EDDY DC tie tripped off line at 1645 on 8/25/05. Return time is unknown. |
EDDY DC tie tripped off line at 1645 on 8/25/05. Return time is unknow. |
There are no scheduled outages at this time. |
There are no scheduled outages at this time. |
Effective 4/29/05, the 35 mw that is available due to a Yearly request that is in study will be made available on a daily basis, either Firm or Non-Firm as ATC allows. Multiple day request will be allowed. |
Effective 4/29/05, the 35 mw that is available due to a Yearly request that is in study will be made available on a daily basis, either Firm or Non-Firm as ATC allows. Multiple day request will be allowed. |
.Effective 4/29/05, the 35 mw that is available due to a Yearly request that is in study will be made available on a daily basis, either Firm or Non-Firm as ATC allows. Multiple day request will be allowed. |
EDDY tie is out of service as of 0900 am 5-27-05.... Not sure how long it will be out at this time.........Effective 4/29/05, the 35 mw that is available due to a Yearly request that is in study will be made available on a daily basis, either Firm or Non-Firm as ATC allows. Multiple day request will be allowed. |
Effective 4/29/05, the 35 mw that is available due to a Yearly request that is in study will be made available on a daily basis, either Firm or Non-Firm as ATC allows. Multiple day request will be allowed. |
The EDDY DC tie will be out of service until May 30..cause unknown. Effective 4/29/05, the 35 mw that is available due to a Yearly request that is in study will be made available on a daily basis, either Firm or Non-Firm as ATC allows. Multiple day request will be allowed. |
The EDDY DC tie will be out of service until May 30, while factory reps are contacted..cause unknown. Effective 4/29/05, the 35 mw that is available due to a Yearly request that is in study will be made available on a daily basis, either Firm or Non-Firm as ATC allows. Multiple day request will be allowed. |
There are no scheduled outages at this time. Effective 4/29/05, the 35 mw that is available due to a Yearly request that is in study will be made available on a daily basis, either Firm or Non-Firm as ATC allows. Multiple day request will be allowed. |
Effective 4/29/05, the 35 mw that is available due to a Yearly request that is in study will be made available on a daily basis, either Firm or Non-Firm as ATC allows. Multiple day request will be allowed. |
Outage schedule for Eddy Tie as follows: The EDDY tie outage has been extended and will possibly be available for schedules on 5/13/05 1800.This is tentative. The tie could be out all next week. Effective 4/29/05, the 35 mw that is available due to a Yearly request that is in study will be made available on a daily basis, either Firm or Non-Firm as ATC allows. Multiple day request will be allowed. |
Outage schedule for Eddy Tie as follows: The EDDY tie outage has been extended and will possibly be available for schedules on 5/13/05 1800.This is tentative. The tie could be out all next week. Effective 4/29/05, the 35 mw that is available due to a Yearly request that is in study will be made available on a daily basis, either Firm or Non-Firm as ATC allows. Multiple day request will be allowed. |
Outage schedule for Eddy Tie as follows: The EDDY tie outage has been extended and will possibly be available for schedules on 5/12/05 1800.This is tentative. The tie could be out all next week. Effective 4/29/05, the 35 mw that is available due to a Yearly request that is in study will be made available on a daily basis, either Firm or Non-Firm as ATC allows. Multiple day request will be allowed. |
Outage schedule for Eddy Tie as follows: The EDDY tie outage has been extended and will possibly be available for schedules on 5/9/05 1800.This is tentative. The tie could be out all next week. Effective 4/29/05, the 35 mw that is available due to a Yearly request that is in study will be made available on a daily basis, either Firm or Non-Firm as ATC allows. Multiple day request will be allowed. |
Outage schedule for Eddy Tie as follows: The EDDY tie outage has been extended and will be available for schedules as of 5/9/05 1800.This is tentative. The tie could be out all next week. Effective 4/29/05, the 35 mw that is available due to a Yearly request that is in study will be made available on a daily basis, either Firm or Non-Firm as ATC allows. Multiple day request will be allowed. |
Outage schedule for Eddy Tie as follows: The EDDY tie outage has been extended and will be available for schedules as of 5/5/05 1700. Effective 4/29/05, the 35 mw that is available due to a Yearly request that is in study will be made available on a daily basis, either Firm or Non-Firm as ATC allows. Multiple day request will be allowed. |
Outage schedule for Eddy Tie as follows: The EDDY tie outage is ended and the tie will be available for schedules as of 5/2/05. Effective 4/29/05, the 35 mw that is available due to a Yearly request that is in study will be made available on a daily basis, either Firm or Non-Firm as ATC allows. Multiple day request will be allowed. |
Outage schedule for Eddy Tie as follows: The EDDY tie outage is ended and the tie is available for schedules as of 2245 5/1/05. Effective 4/29/05, the 35 mw that is available due to a Yearly request that is in study will be made available on a daily basis, either Firm or Non-Firm as ATC allows. Multiple day request will be allowed. |
Outage schedule for Eddy Tie as follows: Limited to 0mw from 4-25-30 @ 0800 thru 4-30-05 @ 1800 . Effective 4/29/05, the 35 mw that is available due to a Yearly request that is in study will be made available on a daily basis, either Firm or Non-Firm as ATC allows. Multiple day request will be allowed. |
Outage schedule for Eddy Tie as follows: Limited to 0mw from 4-25-30 @ 0800 thru 4-30-05 @ 1800 . The 35 mw that is available due to a Yearly request that is in study will be made available on a daily basis, either Firm or Non-Firm as ATC allows. Multiple day request will be allowed. |
Outage schedule for Eddy Tie as follows: Limited to 0mw from 4-25-30 @ 0800 thru 4-30-05 @ 1800 . The 35 mw that is available due to a Yearly request that is in study will be made available on a daily basis, either Firm or Non-Firm as ATC allows. Multiple day request will be considered. |
Outage schedule for Eddy Tie as follows: Limited to 0mw from 4-25-30 @ 0800 thru 4-30-05 @ 1800 . The 35 mw that is available due to a Yearly request that is in study will be made available on a one day next day basis only effective 5/1/05 for weekday scheduling.(Tuesday, Wednesday, Thursday & Friday service will be sold the day prior) Service for the entire weekend will be made available on Fridays. (Service for Saturday, Sunday & Monday will be made available on Friday) |
Outage schedule for Eddy Tie as follows: Limited to 0mw from 4-25-30 @ 0800 thru 4-30-05 @ 1800 . The 35 mw that is available due to a Yearly request that is in study will be made available on a one day next day basis only effective 5/1/05. |
Outage schedule for Eddy Tie as follows: Limited to 0mw from 4-25-30 @ 0800 thru 4-30-05 @ 1800 . The 35 mw that is available due to a Yearly request that is in study will be sold on a one day next day basis only effective 5/1/05. |
Outage schedule for Eddy Tie as follows: Limited to 0mw from 4-25-30 @ 0800 thru 4-30-05 @ 1800 . The 35 mw that is available due to a Yearly request that is in study will be sold on a one day next day basis only effective 5/1/05. |
Outage schedule for Eddy Tie as follows: Limited to 35mw from 4-18-05 thru 4-25-05 @ 0800 Limited to 0mw from 4-25-30 @ 0800 thru 4-30-05 @ 1800 . |
Outage schedule for Eddy Tie as follows: Limited to 35mw from 4-18-05 thru 4-25-05 @ 0800 Limited to 0mw from 4-25-30 @ 0800 thru 4-30-05 1800 . |
Outage schedule for Eddy Tie as follows: Limited to 35mw from 4-18-05 thru 4-25-05 @ 0800 Limited to 0mw from 4-25-30 @ 0800 thru 4-30-05. |
Outage schedule for Eddy Tie as follows: Limited to 35mw from 4-18-05 thru 4-24-05 Limited to 0mw from 4-25-30 @ 0800 thru 4-30-05. |
There are no scheduled outages at this time. |
On 3/8/05 beginning at 10am CST there will be a forced outage on the north 230kv bus at Eddy Co due to a badly leaking 230kv bus pt. |
On 3/8/05 beginning at 10am CST there will be a forced outage on the north 230kv bus at Eddy Co due to a badly leaking 230kv bus pt.. |
There are no scheduled outages at this time. |
The EDDY Co Tie is back to normal. There are no other scheduled outages at this time. |
The EDDy Co Tie is back to normal. There are no other scheduled outages at this time. |
Feb 8 thru Feb 11 the Eddy HVDC tie will be derated to 90MW due to transmission maintenance in the area. |
There are no scheduled outages at this time. |
There are no scheduled outages at this time. |
There are no scheduled outages at this time. |
There are no scheduled outages at this time.br> |
The EDDY Co tie will be out of service from 0500 10/26 to 1700 10/28 for unscheduled maintenance. |
The EDDY Co tie will be out of service from 0500 10/26 to 1700 10/28 for unscheduled maintenance.br> |
There are no scheduled outages at this time. |
There are no scheduled outages at this time.br> |
The Eddy County DC Tie will be out of service for maintenance beginning October 2, 2004 thru October 8, 2004. During this outage there will be ZERO schedules and flows across the tie. |
WSCC EDDY Co normal at this time |
WSCC EDDY Co will not be available until 0000 08/24/2004. |
There are no scheduled outages at this time. |
There is a scheduled outage for the Eddy Co DC tie for the duration of 7/9/04 05:00 - 7/9/04 08:00. |
There are no schedlued outages at this time. |
There are o schedlued outages at this time. |
The EDDY Co DC tie will be out of service for maintenance from March 20th thru March 28th, 2004. |
The EDDY Co DC tie will be out of service for maintenance from 0300 to 0700 CST on Tuesday, Dec 30th, 2003 |
There are no outages scheduled at this time |
No outages scheduled at this time. |
Currently there is a plan to change out transformer bushings and perform other maintenance at the Eddy Co DC tie requiring an outage starting at 8 AM MT Saturday November 1st thru 4PM MT Sunday November 9th. |
Currently there is a plan to change out transformer bushings and perform other maintenance at the Eddy Co DC tie requiring an outage starting at 8 AM MT Saturday November 1st thru 4PM MT Sunday November 9th.i> |
The Eddy Co DC tie tripped at 0831 on 07/18/03 , cause is unknown at this time Duration of outage is undetermined.l. |
There are no outages scheduled at this time. |
| No information at this time. |
| Outage May 3-11, 2003
The Eddy County HVDC Tie will be out of service for maintenance from 0800 CDT on May 3, 2003 until 2000 CDT on May 11, 2003.
Above outage is now over as of 5/09/03 1900 CDT. Eddy County HVDC Tie is now available. |
| Outage May 3-11, 2003
The Eddy County HVDC Tie will be out of service for maintenance from 0800 CDT on May 3, 2003 until 2000 CDT on May 11, 2003.
Above outage is now over as of 5/09/03 1900 CDT. Eddy County HVDC Tie is now available. |
| Outage May 3-11, 2003
The Eddy County HVDC Tie will be out of service for maintenance from 0800 CDT on May 3, 2003 until 2000 CDT on May 11, 2003.
Above outage is now over as of 5/09/03 1900 CDT. Eddy County HVDC Tie is now available. |
| Outage May 3-11, 2003
The Eddy County HVDC Tie will be out of service for maintenance from 0800 CDT on May 3, 2003 until 2000 CDT on May 11, 2003. |
| Outage May 3-11, 2003
The Eddy County HVDC Tie will be out of service for maintenance from 0800 CDT on May 3, 2003 until 2000 on May 11, 2003. |
| Outage May 3-11, 2003
The Eddy County HVDC Tie will be out of service from 0800 CDT on May 3, 2003 until 2000 on May 11, 2003. |
| Outage April 8, 2003
The Eddy County HVDC Tie will be out of service for 5 hours from 0100 CDT until 0600 CDT on April 8, 2003. This outage is for cooling equipment maintenance and preparation for a longer outage in May. Outage May 3-11, 2003 The Eddy County HVDC Tie will be out of service from May 3, 2003 through May 11, 2003. Specific times for the outage will be forthcoming. |
| Outage April 8, 2003
The Eddy County HVDC Tie will be out of service for 5 hours from 0100 CDT until 0600 CDT on April 8, 2003. This outage is for cooling equipment maintenance and preparation for a longer outage in May. Outage May 5-11, 2003 The Eddy County HVDC Tie will be out of service from May 5, 2003 through May 11, 2003. Specific times for the outage will be forthcoming. |
| Outage April 8, 2003
The Eddy County HVDC Tie will be out of service for 5 hours from 0100 CDT until 0600 CDT on April 8, 2003. This outage is for cooling equipment maintenance and preparation for a longer outage in May. Outage May 5-11, 2003 The Eddy County HVDC Tie will be out of service from May 5, 2003 through May 11, 2003. |
| Outage April 8, 2003
The Eddy County HVDC Tie will be out of service for 5 hours from 0100 CDT until 0600 CDT on April 8, 2003. This outage is for cooling equipment maintenance and preparation for a longer outage in May. Outage May 5-11, 2003 |
| Outage April 8, 2003
The Eddy County HVDC Tie will be out of service for 5 hours from 0100 CDT until 0600 CDT on April 8, 2003. This outage is for cooling equipment maintenance and preparation for a longer outage in May. |
| Outage April 8, 2003
The Eddy County HVDC Tie will be out of service for 5 hours from 0100 CDT until 0600 CDT on April 8, 2003. This outage is for cooling equipment maintenance and preparation for a longer outage in May. |
| Outage April 8, 2003
The Eddy County HVDC Tie will be out of service for 5 hours from 0100 CDT until 0600 CDT on April 8, 2003. This outage is for cooling equipment maintenance and preparation for a longer outage in May. |
Outage April 8, 2003 The Eddy County HVDC Tie will be out of service for 5 hours from 0100 CDT until 0600 CDT on April 8, 2003. This outage is for cooling equipment maintenance and preparation for a longer outage in May. |
Outage April 8, 2003 The Eddy County HVDC Tie will be out of service for 5 hours from 0100 CDT until 0600 CDT on April 8, 2003. This outage is for cooling equipment maintenance and preparation for a longer outage in May. |
Outage April 8, 2003 The Eddy County HVDC Tie will be out of service for 5 hours from 0100 CDT until 0600 CDT on April 8, 2003. This outage is for cooling equipment maintenance and preparation for a longer outage in May. EDDY County DC tie. Will be out of service until 1500 on September 12, 2002. |
Outage April 8, 2003 The Eddy County HVDC Tie will be out of service for 5 hours from 0100 CDT until 0600 CDT on April 8, 2003. This outage is for cooling equipment maintenance in preparation for a longer outage in May. EDDY County DC tie. Will be out of service until 1500 on September 12, 2002. |
Outage April 8, 2003 The Eddy County HVDC Tie will be out of service for 5 hours from 0100 CDT until 0600 April 8, 2003. This outage is for cooling equipment maintenance in preparation for a longer outage in May. EDDY County DC tie. Will be out of service until 1500 on September 12, 2002. |
Outage April 8, 2003 The Eddy County HVDC Tie will be out of service for 5 hours from 0100 CDT until 0600 April 8, 2003. This outage is for cooling equipment maintenance in preparation for a longer outage in May. EDDY County DC tie. Will be out of service until 1500 on September 12, 2002. |
EDDY County DC tie. Will be out of service until 1500 on September 12, 2002. |
| EDDY County DC tie. Will be out of service until 1500 on September 12, 2002. |
| EDDY County DC tie. Will be out of service until 1500 on September 12, 2002. Had a forced outage that required parts to be ordered. |
| September 18 Maintenance - 0600 Mountain Time to 1200 Mountain Time The EDDY Co. DC Tie will be taken out of service for maintenance purposes on Wednesday, September 18 at 0600 Mountain time for Maintenance. It is expected that the EDDY Co. DC Tie will return to service at 1200 Mountain Time. No schedules will be allowed to flow across this interface during this outage. |
| July 19 Maintenance - 0000 to 0600 The EDDY Co. DC Tie will be taken out of service for maintenance purposes on Friday, July 19 at 0000 as shown on the SPS OASIS web page (SPS OASIS web page). It is expected that the EDDY Co. DC Tie will return to service at 0600 CDT. No schedules will be allowed to flow across this interface during this outage. |
| March 29 Testing The EDDY Co. DC Tie will be operated for test purposes on Friday, March 29 as shown on the SPS OASIS web page (SPS OASIS web page). It is expected that transmission capacity will be offered by SPP on the EDDY Co. DC Tie concurrent with this DC tie testing. |
| Outage Extended The outage has been extended so additional work can be completed. It is expected the work will be completed on November 2. As more details become available, they will be posted. The Eddy County HVDC Tie is rescheduled to be out for transformer maintenance from 0900 CST on Tuesday, October 30, 2001 until 1800 CST on Wednesday October 31, 2001. This will prevent any schedules through the DC tie. |
| The Eddy County HVDC Tie is rescheduled to be out for transformer maintenance from 0900 CST on Tuesday, October 30, 2001 until 1800 CST on Wednesday October 31, 2001. This will prevent any schedules through the DC tie.
|
| The Eddy County HVDC Tie is scheduled to be out for transformer maintenance from 0900 CDT on Tuesday, October 23, 2001 until 1800 CDT on Wednesday October 24, 2001.
NOTE: The Eddy Co DC tie outage may be moved to October 30th and 31st, 2001. This message will be updated when confirmation is received. |
| The Eddy County HVDC Tie is scheduled to be out for transformer maintenance from 0900 CDT on Tuesday, October 23, 2001 until 1800 CDT on Wednesday October 24, 2001.
NOTE: The Eddy Co DC tie outage may be moved to October 30th and 31st, 2001. This message will be updated when confirmation is received.
|
| The Eddy County HVDC Tie is scheduled to be out for transformer maintenance from 0900 CDT on Tuesday, October 23, 2001 until 1800 CDT on Wednesday October 24, 2001.
|
| CANCELED - The Eddy County HVDC Tie is scheduled to be out for transformer maintenance from 0900 CDT on Tuesday, October 2, 2001 until 1800 CDT on Wednesday October 3, 2001.
|
| The Eddy County HVDC Tie is scheduled to be out for transofrmer maintenance from 0900 CDT on Tuesday, October 2, 2001 until 1800 CDT on Wednesday October 3, 2001.
|
| The Eddy County HVDC Tie is scheduled to be out for breaker maintenance and other work associated with the installation of a cooling system from 0500-0800 MDT (0600-0900 CDT) on Wednesday, July 18, 2001.
|
| The Eddy County HVDC Tie is scheduled to be out for breaker maintenance and other work associated with the installation of a cooling system from 0500-0800 MDT (0600-0900 CDT) on Wednesday, July 18, 2001.
The on-peak hours limitation is being reinstated effective 06/07/2001 until further notice. The scheduled amount across the tie will only be allowed up to 180 MW in either direction from 0900 - 2100 MDT (1000-2200 CDT). |
| The Eddy County HVDC Tie is scheduled to be out for breaker maintenance and other work associated with the installation of a cooling system from 0500-0800 MDT (0600-1900 CDT) on Wednesday, July 18, 2001.
The on-peak hours limitation is being reinstated effective 06/07/2001 until further notice. The scheduled amount across the tie will only be allowed up to 180 MW in either direction from 0900 - 2100 MDT (1000-2200 CDT). |
| The Eddy County HVDC Tie is scheduled to be out for breaker maintenance and other work associated with the installation of a cooling system from 0700-1000 MDT (0800-1100 CDT) on Wednesday, July 18, 2001.
The on-peak hours limitation is being reinstated effective 06/07/2001 until further notice. The scheduled amount across the tie will only be allowed up to 180 MW in either direction from 0900 - 2100 MDT (1000-2200 CDT). |
| The Eddy County HVDC Tie is scheduled to be out for breaker maintenance and other work associated with the installation of a cooling system from 0700-1000 MDT (0800-1100 CDT) on Wednesday, July 18, 2001. The on-peak hours limitation is being reinstated effective 06/07/2001 until further notice. The scheduled amount across the tie will only be allowed up to 180 MW in either direction from 0900 - 2100 MDT (1000-2200 CDT). |
| The Eddy County HVDC Tie is scheduled to be out for breaker maintenance and other work associated with the installation of a cooling system from 0700-1000 MDT (0800-1100 CDT) on Wednesday, July 18, 2001. <> <> The on-peak hours limitation is being reinstated effective 06/07/2001 until further notice. The scheduled amount across the tie will only be allowed up to 180 MW in either direction from 0900 - 2100 MDT (1000-2200 CDT). |
| The on-peak hours limitation is being reinstated effective 06/07/2001 until further notice. The scheduled amount across the tie will only be allowed up to 180 MW in either direction from 0900 - 2100 MDT (1000-2200 CDT). |
| The on-peak hours limitation is being reinstated effective 06/07/2001 until further notice. The scheduled amount across the tie will only be allowed up to 180 MW in either direction from 0900 - 2300 MDT (0800-2200 CDT). |
| The on-peak hours limitation is being reinstated effective 06/07/2001 until further notice. The scheduled amount across the tie will only be allowed up to 180 MW in either direction. |
| Please note that the Eddy Co. HVDC tie will be out of service, for maintenance, from 11/06/2000 through 11/17/2000. The on-peak hours' limitation is being lifted effective October 1. The weather is cooling off and should allow operation at full capacity 24 hours/day prior to maintenance being completed. |
| The Eddy County HVDC Tie has been removed from service, due to a 345 kV transformer problem at Eddy County. The Tie is expected to be out-of-service for at least 2 days. |